登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 土木工程 > 正文

Design of an office building in Nanjing of Jiangsu Province毕业论文

 2021-12-27 20:25:58  

论文总字数:149989字

Graduation Project (Thesis) Report

Topic name

Design of an office building in Nanjing, Jiangsu Province

Institute (Department)

College of Civil Engineering

Speciality

Civil Engineering

Full name

Bissaliyeva Zabira

Student ID

L004160106

Date of departure

2020.02-2020.06

Supervisor

岳健广, 张伟郁


2020-03-01

Design of an office building in Nanjing, Jiangsu Province

Abstract

The graduation project design is the design of office building in Nanjing, Jiangsu Province.

The project is a practical application project of an office building design in Nanjing of Jiangsu Province. The single floor building area is about 429.84 m2, the main body is three spans and 10 floors, and the building area is about 4298.4 m2. The main design scheme is multi-storey reinforced concrete frame structure, and the reasonable design service life of the project is 50 years. The attached are the drawings of the assignment for the general layout of the project and the layout of column network on the standard floor.

In the manual calculation part of the project, the forth axis is selected for calculation. After selection and arrangement of structure, the section size of the component is estimated, then the load is calculated. Using the equivalent base shear method, under horizontal seismic load and moment-distribution method of framework under dead load, live load, 0.5 (live snow) internal forces of framework are estimated. D-value method is used to calculate the wind load and internal force under horizontal seismic action. After the beam end bending moment is adjusted, three general combinations and one combination under seismic action are considered for the calculation of internal force combination. According to the internal force combination results, the calculation of beam and column section reinforcement is carried out. At the end, the reinforcement calculation of AT type plate stair, two-way slab and independent foundation under column is carried out.

Key words: Frame structure, seismic design, load calculation, internal force, calculation of reinforcement, internal force combination, moment-distribution method, D-value method, equivalent base shear method

Contents

Chapter 1 4

1. Architectural design 4

1.1. Design basis 5

1.2. Design content 5

2. Structural design 5

2.1 Structural layout 5

2.2 Cross sectional dimensions of beams and columns 5

2.3 Material strength grade 6

3. Design data 7

3.1 Meteorological data 7

3.2 Engineering geological data 7

3.3 Structure and site seismic effects 7

Chapter 2 8

1. Load calculation 8

1.1. Load information 8

1.2. Live load and Dead load calculation 9

1.3. Wind load 12

1.4. Earthquake action 13

Chapter 3 18

1. Frame internal force calculation 18

1.1 Frame internal force under constant load (dead load) 18

1.2 Frame internal force under live load 25

1.3 Internal force calculation under wind load 42

1.4 Internal force calculation of lateral frame under earthquake 46

2. Frame internal force combination 53

Chapter 4 69

1. Frame beam and column section design 69

1.1 Frame beam section design 69

1.2 Frame column section design 77

Chapter 5 89

1. Stair structure calculation design 89

2. Design of cast-in- place slab 91

Chapter 6 94

1. Foundation design 94

1.1 Load calculation 95

1.2 Base area determination 95

1.3 Earthquake resistance calculation 96

1.4 Foundation deformation considerations 97

2. Infrastructure design 97

2.1 Punching check 98

2.2 Reinforcement 98

Conclusion 100

References 100

Chapter 1

  1. Architectural design
    1. Design basis
  2. Construction instructions
  3. Roof building structure, balcony, stair, toilet, hand basin
  4. Outdoor engineering
  5. Stairs
  6. Aluminum alloy doors and windows
  7. Light partition wall, wall body, floor deformation joint
    1. Design content
  8. Construction view of an office building
  9. First, second and roof floor plan of an office building
  10. 1-6 and 6-1 elevations of an office building
  11. D-A, A-D elevations of an office building
  12. L-L, I-I sections view of office building, stairs detail
  13. Structural design

2.1 Structural layout

2.2 Cross sectional dimensions of beams and columns

(1) Column

According to the "building seismic design specifications" (GB 50011-2010 (2016 edition)) article 6.1.2, the seismic grade of the project for the second; article 6.3.5, the frame column cross-sectional dimensions should comply with the following provisions:

(A) the side length of the rectangular cross-section column, seismic design two should not be less than 400mm;

(B) column shear span ratio should be greater than 2;

(C) column cross-sectional aspect ratio should not be greater than 3; article 6.3.6, column axial pressure ratio should not exceed 0.75;

The initial estimate of the cross-sectional area of the column should meet the following formula:

Where, Nc-considering the axial force design value of the column when the seismic load combination, preliminary estimation can be carried out, Nc=C.N;

C - the influence of bending moment on the axial force of the frame column, the expansion coefficient of the column to take 1.1, 1.2 side column;

N=(12~14)kN/m2 . S, S for the column to bear the floor load area, approximately divided by 1/2 column spacing.

μ - axial pressure ratio, the project should not exceed 0.75.

Middle column:

Take a= 600mm

请支付后下载全文,论文总字数:149989字

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图