深圳凯悦宾馆给水排水工程设计毕业论文
2022-04-09 22:00:21
论文总字数:48537字
摘 要
凯悦宾馆项目所在地在广东深圳,为广东商业用房,地面高度53.2米,总层数17层,地面以上16层,地下一层作为设备房和停车场,不做机动车库,市政水压为2.8公斤。
给水系统分区供水,从市政管网上接一根DN300的引入管,负一层至地上三层为市政管网直供,四至十五层采用水泵供水。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积563m³。建筑高区排水采用污、废水分流制,低区排水采用污废合流制,高区污水与低区废水排入检查井后,经化粪池处理再排入市政污水管。地下室排水经排水沟汇集排至集水井,经潜污泵提升排至检查井。雨水经屋面雨水斗收集后由雨水管排至检查井。
根据规范,该建筑为二类高层建筑,室内消火栓用水量为30L/S,火灾延续时间为3小时。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/S,消防立管管径为DN100.在屋顶设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消火泵的按钮。
该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量30L/S。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分为2个区。采用箱泵一体化消防增压稳压设备(包含18立方米的消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防泵和喷淋泵供水。
关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统
Abstract
Hyatt Regency Hotel project is located in Shenzhen, Guangdong, Guangdong commercial housing, ground height 53.2 m, total number of plies of the 17th floor, 16 floors above ground, underground layer as the equipment room and parking lot, don't do motor garage, municipal water pressure is 2.8 kg.
Water supply system of regional water supply, from the municipal pipe online pick a DN300 introducing pipe, negative a layer to layer for the municipal pipe network direct supply, four 15 layer by water tank. The fire pool adopts steel reinforced concrete structure in the basement pump room outside, the effective volume of fand 563m. High building drain the waste water diversion system, low drainage area with sewage waste combined system, high water and low waste water discharged into the inspection well after, treated in the septic tank again discharged into the municipal sewage tube. The underground chamber drain is collected and discharged to the water collecting well, and the submersible sewage pump is discharged to the inspection well. The rainwater collected from the roof drain rain water pipe row to check well.
According to the specification, the building is two tall buildings, indoor fire hydrant water for 30L/S, the fire duration is 3 hours. Fire hydrant full water column height of 12M, hose length of 25m, water gun nozzle flow 5.16L/S, stand fire pipe diameter was DN100. in roof design test fire a, each indoor fire hydrant boxes are equipped with remote start the fire pump button.
The building adopts wet automatic sprinkler system, spray system design flow 30L/S. Alarm valve is arranged on the basement pump room, all the layers of the design water flow indicator, end water test equipment and signal valve, the signal was sent to fire control center. The automatic water spraying fire extinguishing system in this project is divided into 2 zones. The tank pump integration of fire pressure stabilizing device (including 18 cubic meters of fire water tank) storage fire early 10min automatic sprinkler system, fire hydrant system water fire, the initial fire extinguishing by water supply, post fire from the basement of the fire pump and spray pump water supply.
Keywords: water supply system, drainage system, fire hydrant system, automatic sprinkler system, rain water system
目录
摘 要 1
Abstract 2
第一章 设计说明书 7
1.1凯悦宾馆给排水设计说明书 7
1.1.1工程概况 7
1.1.2设计依据 7
1.1.3设计内容 7
1.2 室内给水工程 8
1.2.1 给水方式选择 8
1.2.2给水系统的组成 8
1.2.3给水管道布置与安装 8
1.3 室内消火栓系统 9
1.3.1 消火栓系统的选择 9
1.3.2.消火栓系统的组成 10
1.3.3消火栓给水管道的安装与布置 10
1.4 自动喷淋工程 10
1.4.1室内自动喷水灭火系统的选择 10
1.4.2 系统组成 11
1.4.3 喷头的选用与布置 11
1.5 排水工程 12
1.5.1排水方式的选择 12
1.5.2排水系统的组成 12
1.5.3排水管道及设备安装要求 12
1.6 雨水系统 13
1.6.1 雨水系统的选择 13
1.6.2 雨水系统的组成 13
1.6.3 雨水管道的布置与敷设 13
第二章 给水系统 14
2.1给水系统计算 14
2.2 水池、水表及水箱的计算 15
2.2.1 水池容积的确定 15
2.2.2 水表选择 15
2.3给水管网水力计算 15
2.3.1低区给水管道水力计算 16
2.3.2高区给水管道水力计算 24
第三章 消火栓系统 31
3.1.设计参数 31
3.2. 消火栓的布置 31
3.3.消火栓系统的计算 32
3.4 最不利点消火栓所需压力和实际射流计算 33
3.5 消防管网水力计算 33
3.5.1 水泵供水工况 33
3.5.2 水箱供水工况 35
3.5.3 消防水箱设置高度的校核 35
3.6 消防水泵的计算与选择 37
3.7 消火栓减压计算 37
3.8室外消火栓 38
第四章 自动喷水灭火系统 39
4.1 喷头的选用与布置 39
4.2 水力计算 39
4.3选泵计算 43
4.4增压泵计算 43
4.5喷淋减压孔板计算 43
第五章 排水系统 45
5.1排水定额及设计秒流量 45
5.1.1排水定额 45
5.1.2设计秒流量 45
5.2排水管道的水力计算 45
5.2.1 高区排水管道水力计算 45
5.2.2 低区排水管道水力计算 54
5.3集水池设计 55
5.3.1 地下室集水坑计算 56
5.3.2 水泵房集水坑计算 56
5.3.2 汽车坡道集水坑计算 56
5.3.4消防电梯集水坑计算 56
5.5化粪池 57
第六章 雨水系统 59
6.1汇水面积计算 59
6.2 雨水量计算 60
6.2.1 暴雨强度计算 60
6.3 设计秒流量 60
6.3.1 雨水管计算 60
6.3.2 溢流口排水量 61
6.4 连接管计算 61
6.5 立管计算 61
6.6 排出管计算 61
参考文献 62
总结 63
请支付后下载全文,论文总字数:48537字