给水系统分区供水,从市政管网上接一根DN100的引入管,负一层至地上二层为市政管网直供,三至十层采用水泵加水箱供水,并预留DN65给水管供空调机房用水。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积468立方。建筑室内排水采用污、废水合流制,室外排水也采用污废合流制,排入检查井后,经化粪池处理再排入市政污水管。卫生间采用多设立管形式,采用专用通气立管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑立面为钢筋混凝土,采用内排水,选择重力流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。
根据规范,该建筑为二类高层建筑,室外消火栓用水量20L/s,室内消火栓用水量30L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。
该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量30L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分2个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。
关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统
Abstract
Water supply system water, from municipal pipe network pick a service pipe DN100, minus one to five floors for the direct supply of municipal pipe network, six to ten layers with no negative-pressure variable-frequency water supply equipment pressurized water DN65 pipe for air conditioner for computer room and reserved water. Fire pool used for reinforced concrete structures placed in basement pumping station outside the effective volume 468 cubic. After combining Construction indoor drainage sewage and waste water, before discharged into the manhole, an outdoor drainage sewage waste was combined, finally convey through a septic tank treatment and then discharged into municipal sewers. Toilet multi-established forms, special ventilation risers, some additional loop vent. Basement drainage flow sewer collection to sump, submersible sewage pump lifting flows into the inspection Chamber. For the reinforced concrete wall building facades, internal drainage, select gravity flow systems, rainwater flow roof rainwater collected by the rain water pipe to manhole.
According to the specifications, the building two high-rise construction, outdoor fire hydrant water 20L/s, 30L/s fire hydrant water consumption, fire life 2h. 12m fire hydrant full water column height, hose length 25m, 5.16L/s water gun nozzle flow, fire the riser tube diameter DN100. Set up a test fire hydrants in roofing, each fire hydrant boxes are equipped with remote start button for fire pump.
Wet automatic fire sprinkler system in the building, spraying system design flow 30L/s. The alarm valve located on the pump room in the basement, the floors are located water flow indicator, test water device and signal the valve at the end, its signal is fed into the fire control centre for processing. Sprinkler system the project divided into 3 zones. Selection box-pump fire booster regulator device integration (including 18 cubic metres of fire water tank) storage initial 10min sprinkler system for fire water, indoor fire hydrant system, initial fire-fighting water tank water supply, late extinguishing the fire pump and sprinkler pumps water from the basement.
Keyword: water-supply system、drainage system、hydrant system、automatic sprinkler system、rainwater system
大丰市某办公楼给排水设计任务书
一、毕业设计(论文)的内容和要求
1、工程概况 大丰市某办公楼为二类高层办公楼,地下一层,地上十层,建筑面积约9910平方米,建筑总高度41.20米。市政管网可以提供的常年资用水头均为0.25Mpa,市政管网不允许直接抽水。地区最大冰冻深度0.45m。城市排水管网为污、雨分流制排放系统。建筑物污水汇集经化粪池处理后排入城市管网集中送至城区集中污水处理厂,市政排水干管DN400,管底埋深2.5~3.0m。 2、设计依据 (1)建筑给水排水设计规范 (GB50015-2003)(2009年版) (2)建筑设计防火规范GB50016 (2006年版) (3)高层建筑防火设计规范GB50045-95 (2005年版) (4)建筑给排水制图标准GB/T50106-2010 (5)自动喷水灭火系统设计规范GB50084-2001 (2005年版) (6)建筑灭火器配置标准GB50140-2005 (7)汽车库、修车库、停车场设计防火规范GB50067-97 (8)室外给水设计规范GB 50013-2006 (9)室外排水设计规范GB 50014-2006 (2011年版) (10)各有关文件及各工程提供的资料。 3、设计内容 本设计包括室内生活给水系统,排水系统(包括雨水系统),消火栓给水系统,自动喷水灭火系统,室外给排水管线综合。 |
二、毕业设计(论文)图纸内容及张数
1、 撰写开题报告(综述); 2、 设计说明书 设计计算书说明书一份,包括以下内容: (1)方案的选择和比较 (2)给水系统水力计算 (3)消火栓系统水力计算 (4)自动喷水灭火系统水力计算 (5)排水系统水力计算 (6)主要设备的选型与计算 3、图纸 (1)室内各层给、排水、消防平面图 (2)生活给水、排水系统图 (3)消防给水、自动喷水灭火系统图 (4)卫生间详图 (5)消防水池、泵房、屋顶水箱详图 (6)室外给排水管网综合平面图 (7)设计总说明 |
三、参考文献
(1)《建筑灭火器配置设计规范》(GB50140—2005) (2)《建筑给水排水设计规范》(GB50015-2003)(2009年版) 请支付后下载全文,论文总字数:34980字