江苏某7层宾馆消防给水系统设计毕业论文
2022-03-18 21:05:21
论文总字数:24466字
摘 要
近年来,安全事故频发,民用公共设施、场所的安全问题越来越得到重视。本设计主要从安全角度对江苏某7层宾馆进行给水系统设计,本设计主要采用两种灭火系统——自动喷水灭火系统、室内消火栓系统。
在进行消火栓设计时,主要围绕室内消火栓的类型、组成、设置原则以及设备的布置和消防用水量的计算等展开。通过全面的思考与计算,选取适当的消火栓型号、确定系统供水管径,以及水枪、水带的型号,并且确定消防水池及水箱的设置。
在自动喷水灭火系统部分主要介绍了湿式系统的设置原则、类型、构成、设备以及布置要求和用水量等。通过查阅相关文献,研读工程图纸,确定喷头的选型、支管管径的选择。自动喷水灭火系统具有结构简单、施工和维护管理方便、灭火及时、立刻出水、建设投资少、管理费用低、适用范围广等优点。占整个自动喷水灭火系统的75%以上,适合安装在常年温度在4—70℃范围内的能用水灭火的构筑物、建筑物中。
关键词:安全 消火栓 自动喷水灭火
ABSTRACT
In recent years, more and more attention has been paid to the safety problems of civil public facilities and places. This design mainly from a security point of view of a seven storey hotel in Jiangsu Province for water supply system design, this design mainly uses two kinds of fire extinguishing system, automatic sprinkler fire extinguishing system and indoor fire hydrant system.
In the design of the fire hydrant, mainly around the types of indoor fire hydrant, composition, setting principles and equipment layout and fire expanded in the calculation of the amount of water. Through comprehensive consideration and calculation, select appropriate fire hydrant types, determine the system of water supply pipe diameter, and hoses, hose model, and determine the setting of fire water tank and water tank.
In the automatic water spraying fire extinguishing system, the principle, type, structure, equipment, arrangement and water consumption of the system are introduced. Through access to relevant literature, reading engineering drawings, determining the nozzle selection, pipe diameter selection. Automatic water spray extinguishing system has the advantages of simple structure, convenient construction and maintenance management, timely fire extinguishing, immediate water outlet, less construction investment, low management cost and wide application range. Accounted for more than seventy-five percent of the entire automatic sprinkler system, suitable for installation in the annual temperature in the range of 70 to 4 C can be the use of water to fire buildings, buildings.
Keywords: safety fire hydrant fire sprinkler
目 录
摘要 i
ABSTRACT i
第1章 课题背景及参考文献综述 1
1.1课题背景 1
1.2参考文献综述 1
1.3相关感悟 2
第2章 消火栓系统设计 3
2.1 设计程序 3
2.2 消火栓灭火系统设计和计算 3
2.2.1 消火栓给水方式的确定 3
2.2.2 选取消火栓的型号以及水带和水枪的使用型号 3
2.2.3 确定消防水枪的充实水柱高度、流量大小、水枪压力大小 4
2.2.4 消火栓口所需水压及水枪流量 4
2.2.5 确定室内消防用水量 7
2.2.6 管网布置 7
2.2.7 绘制图纸 9
2.2.8 确定最不利消火栓及最不利计算管路 9
2.2.9 确定管径 9
2.2.10 水力损失计算 10
2.3 水头损失的计算 12
2.4 消火栓处剩余压力和减压孔板 13
2.4.1 消火栓剩余压力 13
2.4.2 减压孔板 13
2.5 消防水箱容量及设置高度 14
2.5.1 消防水箱 14
2.5.2 消防水池的容量 15
2.5.3 水泵接合器的设置 15
第3章 自动喷水灭火系统的设计 16
3.1设计程序 16
3.2设计过程 16
3.2.1确定作用面积和喷水强度 16
3.2.2 确定喷头的形式和保护面积 18
3.2.3 确定作用面积的形状 18
3.2.4 确定作用面积内的喷头数 19
3.2.5 确定危险等级 20
3.2.6 管径的确定 20
3.2.7 管道总水头损失计算 20
3.2.8 消防水泵的扬程或者系统入口处的供水压力 22
3.2.9 设计作用面积内的平均喷水强度的核对 22
3.2.10 系统的设计流量 22
3.2.11 水箱高度的确定 23
请支付后下载全文,论文总字数:24466字