本设计的内容为二十八层的综合性酒店给水、排水、热水、消防的设计。总占地面积为3.0公顷,建筑面积25000平米左右,建筑高度96.500米。地下一层为设备用房。地上二十八层,一层为大堂,二至五层为办公,六层为设备转换层,七至二十八层为标准间,顶层有电梯机房。

生活给水系统采用下行上给的给水方式。本建筑分区,从地上一层至地上三层采用市政管网供水,地上七层至二十八层采用变频泵供水,分为三区。四到十一层为一区,十二层到十九层为二区,二十层到二十八层为三区。生活排水系统分为生活污水系统和生活废水系统,本建筑只有生活污水,生活污水经室外化粪池处理后排至城市排水管网。室内消火栓系统静水压超100m,分高低区,地下室一层至六层设备层分低区,七层至二十八层为高区。采用水箱和水泵联合供水的临时高压给水系统,并设有消防水箱一个。消防给水系统管道采用独立设置,并且竖向横向成环。超压处采用减压稳压消火栓。该建筑全楼均设自动喷水灭火系统,采用玻璃球闭式标准喷头。消防用水来自高位水箱。喷淋分区要求为120m,故喷淋不分区,必要楼层设减压阀保证水压稳定。本建筑危险等级为中危I级。热水系统采用集中热水供应系统,二十四小时为七至二十八层客户供水,供水方式采用上行下给。进水温度按5℃计算,出水温度按70℃。热水由屋顶水箱供给,为保证热水温度,设回水管。

关键词建筑给水系统、建筑排水系统、消火栓系统、自喷系统、热水系统

Abstract

The content of this design is the design of water supply,sewerage, hot water and fire fighting for the 28-storey comprehensive hotel.It covers an area of 3.0 hectares, with a building area of about 25,000 square meters and a building height of 96.500 meters. The underground floor is equipment space.There are twenty-eight floors on the ground——the first floor is the lobby, the second to the fifth floor is the office, the sixth floor is the equipment conversion floor, the seventh to twenty-eighth floor is the standard room, and the top floor is the elevator room.Domestic Water Supply System adopts downward and upward water supply mode.

The building is divided into three zones by water supply in a subregional way.Municipal pipe network is used to supply water from the ground floor to the ground floor, and frequency conversion pump is used to supply water from the ground floor to the ground floor.Domestic Sewerage System is divided into domestic sewage system and domestic waste water system.This building only has domestic sewage, which is discharged to the urban drainage network after being treated by outdoor septic tank.Indoor fire hydrant system hydrostatic pressure over 100m, sub-high and low areas, the basement layer to six layers of equipment layer low, seven to twenty-eight high area. The use of water tanks and water pumps combined water supply of temporary high pressure water supply system, and a fire water tank. Fire water supply system Pipeline is set independently and vertically forms a ring. Overpressure at the use of decompression and pressure fire hydrant.The building is equipped with automatic sprinkler system, the use of glass ball closed standard nozzle. Fire water comes from the high water tank. Spray partition requirements for the 120m, so the spray is not divided, the necessary floor pressure relief valve to ensure water pressure stability. The building grade is Grade I. Hot water system using centralized hot water supply system, twenty-four hours for the seven to twenty-eight customers water supply, water supply and living with the way to use under the water. Water temperature by 5 ℃, the water temperature by 70 ℃. Hot water is supplied by the roof tank, to ensure hot water temperature, set back to the water pipe.

Key word: Building water supply systems, Building drainage systems, Fire hydrant systems, Self - spray systems, Hot water systems

目 录

第1章 绪论 1

1.1目的及意义 1

1.2国内外研究现状 1

1.3设计任务 2

1.4设计文件及设计资料 2

1.5设计内容 2

1.6设计依据 3

1.7设计成果 4

第2章 设计说明书 5

2.1给水系统设计 5

2.1.1给水资料 5

2.1.2方案比选 5

2.1.3水箱容积 6

2.2排水系统设计 6

2.3消火栓系统设计 6

2.4自动喷水灭火系统 9

2.5热水系统 11

第3章.设计计算书 13

3.1给水系统计算 13

3.1.1最高日用水量与最高日最大时用水量计 13

3.1.2管网水力计算 13

3.1.3水泵选型 30

3.2排水系统计算 30

3.2.1排水水力计算 30

3.2.2化粪池计算 40

3.3消防系统 40

3.3.1 消防水箱容积 40

3.3.2 消防储水池计算 41

3.3.3消火栓管网水力计算 41

3.3.4屋顶增压稳压设备 45

3.3.5减压措施 46

3.3.6水泵接合器计算 46

3.4自动喷水灭火系统水力计算 47

3.4.1喷头的布置 47

3.4.2自动喷水灭火系统水力计算 48

3.4.3喷淋减压 58

3.4.4校核最不利喷头 58

3.4.5局部增压 59

3.5室内热水系统 60

3.5.1热水用量计算 60

3.5.2耗热量计算 60

3.5.3热媒耗热量计算 60

3.5.4热水贮存器容积计算 61

3.5.5热交换设备计算 61

3.5.6机械循环水力计算 72

3.5.7 膨胀管计算 72

结论 73