南京华泰大厦给水排水工程设计毕业论文
2022-01-05 20:40:41
论文总字数:19459字
摘 要
本设计是南京华泰大厦建筑给水排水设计,任务内容包括给水系统、排水系统、消火栓系统、自动喷淋系统。
该建筑为商业住宅一类建筑,建筑高度69.40m,火灾危险等级为中危I级。所以将给水供给分为市政直供,变频泵加压供给中区3-11层,变频泵加压供给高区12-21层。给水管材采用入户管4级PPR管、立管采用铸铁管。
排水系统采用合流制,室内一层标高0m以上污废水经重力自流排至室外检查井,地下室污废水经集水坑内潜污泵提升至室外检查井,排水立管接有大便器的通气方式为专用通气管或侧墙通气;排水横管采用普通UPVC塑料管,立管采用螺旋降噪UPVC塑料管,雨水斗为87式雨水斗,雨水立管为UPVC塑料管。
消防系统采用临时高压,在地下室设水泵,屋顶设消防水箱。在地下一层,二层,顶层水平成环,其他竖向成环。管材采用焊接钢管钢管。自动喷水灭火系统根据地下室防火卷帘设两个区,管材为热镀锌钢管。
关键词:商业住宅建筑 ;高层建筑给水排水;给水分区
Water supply and drainage engineering design of Nanjing Huatai Mansion
Abstract:
This design is the water supply and drainage design of Nanjing Huatai Building. The task includes water supply system, drainage system, hydrant system and automatic spray system.
The building is a class I commercial residential building with a building height of 69.40m and a fire risk level of medium risk I. Therefore, the water supply is divided into municipal direct supply, frequency conversion pump pressurization supply layer 3-11 in the middle area, and frequency conversion pump pressurization supply layer 12-21 in the high area. The water supply pipes are PPR pipes of grade 4 for household pipes and cast iron pipes for risers.
The drainage system adopts the combined flow system. The waste water above the elevation of 0m on the first floor of the room is discharged to the outdoor inspection well by gravity, and the waste water in the basement is lifted to the outdoor inspection well by the submersible sewage pump in the sump. The ventilation mode of the drainage riser connected with the defecator is the special ventilation pipe or side wall ventilation; the horizontal drainage pipe is ordinary UPVC Plastic pipe, the riser is spiral noise reduction UPVC Plastic pipe, and the rainwater bucket is 87 type Rainwater hopper and rainwater riser are UPVC Plastic pipes.
The fire protection system adopts temporary high pressure, with water pump in the basement and fire water tank on the roof. In the first and second floors of the underground, the top layer is horizontally in a ring, and the others are vertically in a ring. Welded steel pipe is adopted as the pipe. The automatic sprinkler system is provided with two areas according to the basement fire shutter, and the pipe material is hot-dip galvanized steel pipe.
Key words: commercial residential buildings; water supply and drainage of high-rise buildings; water supply division
目录
摘要 2
Abstract 3
第一章 设计任务 7
1.1设计基础资料和任务 7
1.1.1 相关资料 7
1.1.2设计主要内容 7
1.1.3应提交的设计文件 7
第二章 设计说明 9
2.1给水工程 9
2.1.1给水系统的选择 9
2.1.2系统的组成 9
2.1.3加压设备 9
2.1.4 管道布置要求 10
2.2排水工程 10
2.2.1 系统选择 10
2.2.2 系统组成 10
2.2.3 主要设备 10
2.2.4管道安装要求 10
2.3消防给水 11
2.3.1 室内消火栓系统 11
2.3.2自动喷淋系统 12
2.3.3消防管道敷设要求 12
第三章 计算说明 13
3.1室内给水系统水力计算 13
3.1.1给水用水定额及时变化系数 13
3.1.2最高日用水量 13
3.1.3最高日最高时用水量 14
3.1.4设计秒流量 14
3.1.6室内给水管道水力计算 15
3.1.7选泵 20
3.2室内排水系统水力计算 20
3.2.1一层卫生间 20
3.2.2二层卫生间排水计算 22
3.2.3标准层卫生间排水计算 24
3.2.4地下室排水 27
3.2.5化粪池 27
3.2.6雨水排水计算 28
3.3消火栓系统计算 30
3.3.1消火栓的布置 30
3.3.2水枪喷嘴处所需水压 30
3.3.3水枪喷嘴的出流量 30
3.3.4水带阻力 31
3.3.5消火栓口所需的水压 31
3.3.6校核 31
3.3.7水力计算 31
3.3.8消火栓水泵的选取 33
3.3.9减压 33
3.3.10消防水箱 34
3.3.11消防贮水池 34
3.4室内喷淋系统计算 34
3.4.1喷淋布置 34
3.4.2标层喷淋计算 34
3.4.3水泵选择 36
3.4.4 减压 37
3.4.5 报警阀及喷头 37
3.4.6水泵结合器 37
结语 38
参考文献 39
致谢 40
第一章 设计任务
1.1设计基础资料和任务
1.1.1 相关资料
南京华泰大厦主体建筑为地上二十一层,地下一层。地下一层为车库、地上一至二层为商场,三至二十一层为住宅,其中二十一层为跃层,总建筑面积19800m2,建筑总高度73.70m。
市政自来水压力约为: 0.28MPa。