给水系统分区供水,从市政管网上接一根DN100的引入管,负一层至地上四层为市政管网直供,五至十七层采用设水泵的供水方式,并预留DN65给水管供空调机房用水。消防水池采用钢筋混凝土结构,与地下室泵房相连,有效容积432立方米。建筑室内排水采用污、废水分流制,室外排水采用污废分流制,排入检查井后,再排入市政污水管。卫生间采用多设立管形式,采用专用通气立管,部分采用伸顶通气管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑立面为混凝土墙体,采用外排水,选择重力半有压流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为二类高层建筑,室外消火栓用水量20L/s,室内消火栓用水量30L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量20L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。由于每个报警阀不能超过800个喷头,所以本工程的自动喷水灭火系统分四个区,分别为地下室到2层,3到5层,5到10层,11到17层四个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

Water supply system water, from municipal pipe network pick a service pipe DN100, minus one to four floors for the direct supply of municipal pipe network, five to ten layers with pump water supply mode. DN65 pipe for air conditioner for computer room and reserved water. Fire pool used for reinforced concrete structures placed in basement pumping station outside the effective volume 432 cubic. Construction indoor drainage-diversion of sewage, waste water, an outdoor drainage sewage waste combined, after discharged into the manhole, septic tank treatment and then discharged into municipal sewers. Toilet multi-established forms, special ventilation risers, some additional loop vent. Basement drainage flow sewer collection to sump, submersible sewage pump lifting flows into the inspection Chamber. For the whole glass curtain wall building facades, internal drainage, select half-pressure of gravity flow systems, rainwater flow roof rainwater collected by the rain water pipe to manhole.

According to the specifications, the building two high-rise construction, outdoor fire hydrant water 20L/s, 30L/s fire hydrant water consumption, fire life 2h. 12m fire hydrant full water column height, hose length 25m, 5.16L/s water gun nozzle flow, fire the riser tube diameter DN100. Set up a test fire hydrants in roofing, each fire hydrant boxes are equipped with remote start button for fire pump.

Wet automatic fire sprinkler system in the building, spraying system design flow 20L/s. The alarm valve located on the pump room in the basement, the floors are located water flow indicator, test water device and signal the valve at the end, its signal is fed into the fire control centre for processing. Sprinkler system the project divided into 4 zones. Selection box-pump fire booster regulator device integration (including 18 cubic metres of fire water tank) storage initial 10min sprinkler system for fire water, indoor fire hydrant system, initial fire-fighting water tank water supply, late extinguishing the fire pump and sprinkler pumps water from the basement

Keyword: water-supply system、drainage system、hydrant system、automatic sprinkler system、rainwater system

淮安市长运公司办公大楼给排水设计任务书

  1. 工程概况

本课题为淮安市长运公司办公大楼设计,该建筑属高层公共建筑,建筑已完成条件图设计,现要求给排水专业对其进行给排水设计。

该建筑共十七层,建筑总高度为73.83m,地上十七层,地下一层。地下层设生活消防水池并有水泵房,并有自动报警装置。建筑因为是公共建筑,所以除设有消水栓系统外,还设有自动喷水灭火系统。该建筑的北侧、南侧50M处分别有一市政给水管道经过,管顶标高为-1.5M,管径为DN200,供水最低压力为25M水头;建筑北侧55M、58M处分别有一市政污水管、市政雨水管,管顶标高分别为-2.0M和-3.0M。

二、设计依据

1.建筑给水排水设计规范GBJ50015-2003(2009年版);

2.建筑设计防火规范GB50016-2006(2006年版);

3.高层民用建筑设计防火规范GB50045-95(2005版);

4.给排水制图标准GB/T50106-2001

5.自动喷水灭火系统设计规范GB50084-2001(2005版);

6.有关文件及各工程提供的资料,包括:10张平面图,4张立面图。

三、设计内容

本设计应包括生活给水系统、消防系统(包括消火栓系统和自动喷水灭火系统)、生活排水系统、雨水系统。

四、完成的工作量

  1. 设计计算说明书一本,包括如下内容:

(1)方案的选择和比较;

(2)给水系统水力计算;

(3)排水系统水力计算;

(4)消火栓系统水力计算;

(5)自动喷水灭火系统水力计算;

(6)主要设备的选型与计算;

(7)格式:封面,目录,英文摘要,中文摘要,正文,参考文献。

  1. 图纸

(1) 图纸目录 1 张

(2) 给排水设计及施工说明 1 张