登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给排水科学与工程 > 正文

南京工业大学科技园研发楼给排水工程设计毕业论文

 2022-05-05 20:41:41  

论文总字数:32484字

摘 要

给水系统分区供水,从市政管网上接一根DN100的引入管,负一层至地上五层为市政管网直供,六至十层采用无负压变频供水设备加压供水。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积452.16立方。建筑采用合流排水体制,污水可直接排入城市排水管网集中送至污水处理厂。卫生间采用多设立管形式,采用专用通气立管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑立面为全玻幕墙,采用内排水,选择重力半有压流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为二类高层建筑,室外消火栓用水量20L/s,室内消火栓用水量30L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量27.69L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分2个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

Water supply system water, from municipal pipe network pick a service pipe DN100, minus one to five floors for the direct supply of municipal pipe network, six to ten layers with no negative-pressure variable-frequency water supply equipment pressurized water. Fire pool used for reinforced concrete structures placed in basement pumping station outside the effective volume 452.16 cubic. Construction indoor drainage-diversion of sewage, waste water, an outdoor drainage sewage waste combined, after discharged into the manhole, septic tank treatment and then discharged into municipal sewers. Toilet multi-established forms, special ventilation risers, some additional loop vent. Basement drainage flow sewer collection to sump, submersible sewage pump lifting flows into the inspection Chamber. For the whole glass curtain wall building facades, internal drainage, select half-pressure of gravity flow systems, rainwater flow roof rainwater collected by the rain water pipe to manhole.
According to the specifications, the building two high-rise construction, outdoor fire hydrant water 20L/s, 30L/s fire hydrant water consumption, fire life 2h. 12m fire hydrant full water column height, hose length 25m, 5.16L/s water gun nozzle flow, fire the riser tube diameter DN100. Set up a test fire hydrants in roofing, each fire hydrant boxes are equipped with remote start button for fire pump.
Wet automatic fire sprinkler system in the building, spraying system design flow 40L/s. The alarm valve located on the pump room in the basement, the floors are located water flow indicator, test water device and signal the valve at the end, its signal is fed into the fire control centre for processing. Sprinkler system the project divided into 2 zones. Selection box-pump fire booster regulator device integration (including 18 cubic metres of fire water tank) storage initial 10min sprinkler system for fire water, indoor fire hydrant system, initial fire-fighting water tank water supply, late extinguishing the fire pump and sprinkler pumps water from the basement

Keyword: water-supply system、drainage system、hydrant system、automatic sprinkler system、rainwater system

南京工业大学科技园研发楼给排水工程设计任务书

  1. 工程概况

该建筑总高度为42.6m,地上十层,地下一层。建筑一层层高5.4米,标准层3.8米,地下室层高3.6米,建筑标准层面积786.7㎡,地上总建筑面积8010㎡,地下一层面积为1361㎡

  1. 给水水源

本建筑以城市给水管网作为水源,从市政管网取水,供水水压为0.28MPa。

(2)排水条件

建筑采用合流排水体制,污水可直接排入城市排水管网集中送至污水处理厂。

二、设计依据

(1)《建筑给水排水设计规范》GB50015-2003(2009年版)

(2)《建筑设计防火规范》GB50016 (2006年版)

(3)《高层民用建筑设计防火规范》GB50045-95 (2005年版)

(4)《消防给水及消火栓系统技术规范》GB50974-2014

(5)《建筑灭火器配置设计规范》GB50140-2005

(6)《给排水制图标准》GB/T50106-2001

(7)《自动喷水灭火系统设计规范》GB50084-2001 (2005年版)

(8)各有关文件及各工程提供的资料。

三、设计内容

1.生活给水系统

2.消防系统(包括消火栓系统和自动喷水灭火系统)

3.生活排水系统

4.雨水系统

四、完成的工作量

  1. 设计计算说明书一本,包括如下内容:

方案的选择和比较;

给水系统水力计算;

排水系统水力计算;

消火栓系统水力计算;

自动喷水灭火系统水力计算;

主要设备的选型与计算;

格式:封面,目录,英文摘要,中文摘要,正文,参考文献。

  1. 图纸

(1) 图纸目录 1 张

(2) 给排水设计及施工说明 1 张

请支付后下载全文,论文总字数:32484字

您需要先支付 80元 才能查看全部内容!立即支付

企业微信

Copyright © 2010-2022 毕业论文网 站点地图